CONDUCTIVE LEAKINESS | area (m2) |
U-value (W/m2/°C) |
leakiness (W/°C) |
---|---|---|---|
Horizontal surfaces | |||
Pitched roof | 48 | 0.6 | 28.8 |
Flat roof | 1.6 | 3 | 4.8 |
Floor | 50 | 0.8 | 40 |
Vertical surfaces | |||
Extension walls | 24.1 | 0.6 | 14.5 |
Main walls | 50 | 1 | 50 |
Thin wall (5in) | 2 | 3 | 6 |
Single-glazed doors and windows | 7.35 | 5 | 36.7 |
Double-glazed windows | 17.8 | 2.9 | 51.6 |
Total conductive leakiness | 232.4 |
VENTILATION LEAKINESS | volume (m3) |
N (air-changes per hour) |
leakiness (W/°C) |
---|---|---|---|
Bedrooms | 80 | 0.5 | 13.3 |
Kitchen | 36 | 2 | 24 |
Hall | 27 | 3 | 27 |
Other rooms | 77 | 1 | 25.7 |
Total ventilation leakiness | 90 |
To compare the leakinesses of two buildings that have different floor
areas, we can divide the leakiness by the floor area; this gives the heat-loss
parameter of the building, which is measured in W/°C/m2. The heat-loss
parameter of this house (total floor area 88 m2) is
3.7 W/°C/m2.
Let’s use these figures to estimate the house’s daily energy consumption
on a cold winter’s day, and year-round.
On a cold day, assuming an external temperature of -1 °C and an internal
temperature of 19 °C, the temperature difference is ΔT = 20 °C. If
this difference is maintained for 6 hours per day then the energy lost per
day is
322 W/°C × 120 degree-hours ≅ 39 kWh.
If the temperature is maintained at 19 °C for 24 hours per day, the energy
lost per day is
155 kWh/d.
To get a year-round heat-loss figure, we can take the temperature demand
of Cambridge from figure E.5. With the thermostat at 19 °C, the